AC circuit breakers on DC circuits


Hi all

This will spark some discussion Im sure.

I have viewed this youtube entry https://www.youtube.com/watch?v=kRB7Z66brO0

Its self explanatory but it seems we can use an AC breaker on DC (just double the rating)

I guess the thermal side of the breaker will operate first, from magnetic theory Im sure the laminated poles still produce a strong enough field to trip the breaker as well.

I would love to hear others opinions. I have a 60 amp AC breaker on the DC side of my inverter (only wanted to use it as a switch to isolate the DC.

Interesting....

Safe travels

 

 



__________________

P B Crockart EX RAAF Electrician,

Aircraft Avionics tech. Senior high school teacher.

Live long and Prosper



Guru

Status: Offline
Posts: 1743
Date:

Hi Phil

Yes, Ac breakers  & switchs can be used on DC but not necessarily ALL

Makers will usualy show the DC rating if they consider their's is suitable

  It is based on both voltage & amps. but the trip current in both situations will be very similar

It is the arc rupturing abilty [which depends on design] that is the major consideration

There is no hard & fast formula for that

Which operates first will depend on the current

Thermal trip covers normal overloads but always has a time delay

The magnetic trip is fast acting ,more for quick disconnect of sudden excess currents ,such as a short circuits

All Cbs also have a MAX current interupt rating, one they can handle without damage to themselves .

The current that could occur is determined by :

The max short circuit current available fron the source

The actual circuit impedance

 

PeterQ



-- Edited by oldtrack123 on Friday 22nd of August 2014 12:42:24 PM

__________________


Guru

Status: Offline
Posts: 4375
Date:

Clipsal rate theirs at 48V DC.
Note however they that the time to trip will be Root2 times as long (about 1.4X).

That is an increase in trip TIME, not an increase in RATING as per the OP.

I used 240V DC circuit breakers in the OKA DC wiring, but I avoid using them as switches to break flowing current in order to reduce the frequency of arcing.
I have yet to experience a failure in 10 years of use.

Cheers,
Peter



-- Edited by Peter_n_Margaret on Friday 22nd of August 2014 04:28:22 PM

__________________

OKA196, 4x4 'C' Class, DIY, self contained motorhome. 960W of solar, 400Ah of AGMs, 310L water, 280L fuel. https://www.oka4wd.com/forum/members-vehicles-public/569-oka196-xt-motorhome
 

 



Guru

Status: Offline
Posts: 1743
Date:

Peter_n_Margaret wrote:

Clipsal rate theirs at 48V DC.
Note however they that the time to trip will be Root2 times as long (about 1.4X).

That is an increase in trip TIME, not an increase in RATING as per the OP.

 
Cheers,
Peter



-- Edited by Peter_n_Margaret on Friday 22nd of August 2014 04:28:22 PM


 

HI Peter

Perhaps you have misunderstood some data as the thermal magnetic trip units fitted to a.c. circuit-breakers are also suitable to be used with direct current.

The thermal protection does not change with reference to its tripping characteristic as the bimetal strips of the trip units are influenced by the heating caused by the current flow, it does not matter whether AC or DC .

I think you may be confusing AC peak Current with RMS values

  The peak curent is 1.4times the RMS but when we say XX amps  with AC we are referring to the RMS value.

IxIx R= P[Watts] is the same in each case each case 

However the MAGNETIC trip function will change  under short circuit conditions, due to ferromagnetics involved with AC

Generally the reaction trip time  will be faster with DC than AC.

The big reason for derating with DC is ARC suppression.

 

PeterQ



__________________


Guru

Status: Offline
Posts: 4375
Date:

The root2 X trip time was Clipsal's figure, not mine, unless I misread it???
Will see if I have a copy.....

Cheers,
Peter

__________________

OKA196, 4x4 'C' Class, DIY, self contained motorhome. 960W of solar, 400Ah of AGMs, 310L water, 280L fuel. https://www.oka4wd.com/forum/members-vehicles-public/569-oka196-xt-motorhome
 

 



Guru

Status: Offline
Posts: 4375
Date:

Found this updates.clipsal.com/clipsalonline/Files/Brochures/I0000097.pdf
Quotes the 48VDC, but does not describe any other DC operating characteristics.

Cheers,
Peter

__________________

OKA196, 4x4 'C' Class, DIY, self contained motorhome. 960W of solar, 400Ah of AGMs, 310L water, 280L fuel. https://www.oka4wd.com/forum/members-vehicles-public/569-oka196-xt-motorhome
 

 



Guru

Status: Offline
Posts: 4706
Date:

Hmmmmm... I'd be a bit cautious with the expectation that all MCBs will
operate in a similar manner on DC as they do on AC.

Certainly in regard to the thermal tripping the DC will equal the RMS and
all should be good but I'm not so sure about the magnetic aspect.

Page 7 of the above PDF shows the MCB design and the magnetic
tripping is performed by a solenoid the coil of which, I assume, is designed
with 240V AC in mind. Additionally the "Specifications" section of:

www.clipsal.com/Trade/Products/ProductDetail

specifies the "Voltage type" as "AC" and makes no mention of DC.

Given that the only purpose in fitting a MCB is to be as certain as
possible that it will *work* then I would seek e-mail confirmation from
the manufacturers for each model which you intend to use on DC.

MH


__________________

 

"I beseech you in the bowels of Christ think it possible you may be mistaken"

Oliver Cromwell, 3rd August 1650 - in a letter to the General Assembly of the Kirk of Scotland

KFT


Guru

Status: Offline
Posts: 2437
Date:

Think I would be looking to NHP products to be sure to get something eminently suited to the task.

frank

__________________

Avagreatday.

Kathy and Frank currently at Home near Quirindi NSW



Guru

Status: Offline
Posts: 720
Date:

Thanks folks for a lively discussion, I have had a look at some old text books and agree that the slower thermal aspect of the breaker should open the circuit. The magnetic however may not be as efficient due to not enough flux being generated (Flux = I x N) and at 12V probably not enough to stick to a fridge. Then again under a short circuit who knows? However as I have stated I only wanted to isolate the DC and if its a safety measure as well I get a bonus.

Cheers and safe travels



__________________

P B Crockart EX RAAF Electrician,

Aircraft Avionics tech. Senior high school teacher.

Live long and Prosper



Guru

Status: Offline
Posts: 1743
Date:

Mike Harding wrote:

Hmmmmm... I'd be a bit cautious with the expectation that all MCBs will
operate in a similar manner on DC as they do on AC.

Certainly in regard to the thermal tripping the DC will equal the RMS and
all should be good but I'm not so sure about the magnetic aspect.

Page 7 of the above PDF shows the MCB design and the magnetic
tripping is performed by a solenoid the coil of which, I assume, is designed
with 240V AC in mind. Additionally the "Specifications" section of:

www.clipsal.com/Trade/Products/ProductDetail

specifies the "Voltage type" as "AC" and makes no mention of DC.

Given that the only purpose in fitting a MCB is to be as certain as
possible that it will *work* then I would seek e-mail confirmation from
the manufacturers for each model which you intend to use on DC.

MH


 

HI Mike

Your point is valid with regard to the MAGNETIC trip,  if used on a different voltage to the designed voltage

One designed for 240V would be pretty well useles on 12V, either AC or DC

It will trip under short circuit conditions but only due to the THERMAL trip

 

To other readers

DC circuit breakers NEED better ARC quenching than AC breakers.[for the same voltages ]

That is the primary reason why ,when used on DC, the voltage rating is so LOW compared to the A C designed rating



-- Edited by oldtrack123 on Saturday 23rd of August 2014 01:07:49 PM

__________________


Guru

Status: Offline
Posts: 1531
Date:

Without wanting to derail the original topic too far, can anyone tell me why many DC thermal circuit breakers have "Batt" and "Aux" labels on their terminals. Given that they operate by heat build up from excessive current, distorting a metal (stainless?) plate which has been punched to give it a dish shape (yes i pulled a few apart ;) ), why does it matter which way the current flows? Or is it maybe that they are marked to facilitate circuit tracing once they are installed?

__________________


Guru

Status: Offline
Posts: 4706
Date:

In the case of there being only a thermal tripping mechanism then I
can see no reason why direction of current flow would matter - heat
is heat.

However many (most?) DC MCBs are combined magnetic and thermal:

bit.ly/1AIJXIe

and in these cases it is essential that current flow is in the
specified direction in order that the magnetic fields have the
required polarity.

It may simply be that cheap MCBs are produced which don't include the
magnetic aspect but use the same plastic moulding? Or, maybe, the
manufacturers tired of people asking about the polarity so specified
one anyway? :)

MH



__________________

 

"I beseech you in the bowels of Christ think it possible you may be mistaken"

Oliver Cromwell, 3rd August 1650 - in a letter to the General Assembly of the Kirk of Scotland



Guru

Status: Offline
Posts: 1743
Date:

03_troopy wrote:

Without wanting to derail the original topic too far, can anyone tell me why many DC thermal circuit breakers have "Batt" and "Aux" labels on their terminals. Given that they operate by heat build up from excessive current, distorting a metal (stainless?) plate which has been punched to give it a dish shape (yes i pulled a few apart ;) ), why does it matter which way the current flows? Or is it maybe that they are marked to facilitate circuit tracing once they are installed?


 

HI Troopy

They are  polarised so the magnetic arc blowout system pushes the arc in the right direction to break it.

  That can be very important if they are to break the arc before it does damage to the breaker itself

Qualty breakers designed for DC operation usualy do have a magnetic arc blow out

PeterQ



-- Edited by oldtrack123 on Sunday 24th of August 2014 11:11:12 AM

__________________


Guru

Status: Offline
Posts: 1531
Date:

Sorry Peter, I should have been more specific. I meant the common automotive types like these.

DC CB.jpgDC CB2.jpg



Attachments
__________________


Guru

Status: Offline
Posts: 1531
Date:

Still no takers for this query?

__________________


Guru

Status: Offline
Posts: 1743
Date:

03_troopy wrote:

Still no takers for this query?


 

HI

I have not pulled  either type apart , so cannot say if either do gave a small permanent magnet to assist arc  blow out.

I doubt the small elcheapo  has any form just relies on luck Or the larger copper as a a heat sink

The better one could easily have a small permanent magnet   or even a  basic deionizing chamber [ series of ferrous  metal plate which become magnetised by the current & breaks the arc up into  small sections.

An other option used by some is a multi Arc gap, ie two  or more sets of contacts in series

But without opening them I realy cannot say for certain.

 

PeterQ

 

 

 

 

 

 

 

 

 

 

 

 

 



-- Edited by oldtrack123 on Thursday 28th of August 2014 10:17:05 PM

__________________


Guru

Status: Offline
Posts: 1531
Date:

oldtrack123 wrote:
03_troopy wrote:

Still no takers for this query?


 

HI

I have not pulled  either type apart , so cannot say if either do gave a small permanent magnet to assist arc  blow out.

I doubt the small elcheapo  has any form just relies on luck Or the larger copper as a a heat sink

The better one could easily have a small permanent magnet   or even a  basic deionizing chamber [ series of ferrous  metal plate which become magnetised by the current & breaks the arc up into  small sections.

An other option used by some is a multi Arc gap, ie two  or more sets of contacts in series

But without opening them I realy cannot say for certain.

 

PeterQ

 

 

 

 Peter, neither of the 2 shown have any magnets and have only the metal plate that acts as the breaker. The query came up when connecting the manually re-settable one in a dual battery setup, where the limited current would be from the auxiliary battery back to the main battery when using the override function of the smart isolator. One bloke wanted to connect the main battery to the BAT terminal and the AUX (load) terminal to the smart isolator. I was thinking that because the current would be in the direction of Auxiliary battery to main battery (flat main battery) maybe it should be connected the opposite way round. But no-one can give a definitive answer on it it so far (with a reason why). To be honest, I really can't see any reason why it wouldn't work both directions.

 

 

 

 

 

 

 

 



-- Edited by oldtrack123 on Thursday 28th of August 2014 10:17:05 PM


 



__________________


Guru

Status: Offline
Posts: 1743
Date:

HI Troopy

12vDC cannot draw a very long arc, so as long as the break gap is long enough & the break is fast enough,a sustained arc is unlikely

But that can change when the voltage gets above 24VDC or the load is highly inductive[ motors or coils with ferrous cores  

 

PeterQ



__________________


Guru

Status: Offline
Posts: 1531
Date:

oldtrack123 wrote:

HI Troopy

12vDC cannot draw a very long arc, so as long as the break gap is long enough & the break is fast enough,a sustained arc is unlikely

But that can change when the voltage gets above 24VDC or the load is highly inductive[ motors or coils with ferrous cores  

 

PeterQ


 Yes peter that is also true. thanks. ;)



__________________


Senior Member

Status: Offline
Posts: 134
Date:

here is a link to NHP breaker at all good electrical suppliers
single pole up to 48volt dc and 2 pole 110 dc





www.nhp.com.au/files/editor_upload/File/Brochures/Business-Specific/easy-selection-guides/NHPNTUMCBAUSESG.pdf

__________________


Guru

Status: Offline
Posts: 5388
Date:

I am not an Auto or normal Electrician
I can only go by what the description says

I have recently purchased 12 VDC 30 Amp circuit breakers
From the description I will assume that there is a type of 30 amp fuse inside

I had normal inline blade fuses, but these circuit breakers will give me the ability to isolate, the following circuits, easier

Roof solar panel, positive wire before the DC/DC charger
12 volt upright fridge, positive wire, at the batteries
12 volt merit (ciggy type) socket, positive wire, (for my chest fridge/freezer if I need to use it), at the batteries end

The inline blade fuses would have done the same isolation, at a much cheaper price
The circuit breakers give me ease of isolation/re-powering

12 volt circuit breaker.png



__________________

Tony

It cost nothing to be polite



Guru

Status: Offline
Posts: 1743
Date:

Tony Bev wrote:

I am not an Auto or normal Electrician
I can only go by what the description says

I have recently purchased 12 VDC 30 Amp circuit breakers
From the description I will assume that there is a type of 30 amp fuse inside

I had normal inline blade fuses, but these circuit breakers will give me the ability to isolate, the following circuits, easier

Roof solar panel, positive wire before the DC/DC charger
12 volt upright fridge, positive wire, at the batteries
12 volt merit (ciggy type) socket, positive wire, (for my chest fridge/freezer if I need to use it), at the batteries end

The inline blade fuses would have done the same isolation, at a much cheaper price
The circuit breakers give me ease of isolation/re-powering

12 volt circuit breaker.png


Elcheopo 12V thermal circuit are just  a thermal switch .often using just the moving contact arm itself as the bimetal thermal trip 

Auto rest types simply close the contacts with arm cools down & something that should not be normally used except in situations as vehicle headlights 

Manual  reset require manual resetting to latch in . Such should be used for most applications as you will be aware they have tripped & investigate why

Polarity again could depend on design , but with most the  Pos [usually the fixed] contact,  in breaker will be larger or have a heat sink to absorb the greater heat generated by  arc @ the Pos contact face

  Better quality Dc breakers especial for voltage above 24V will usually have some form of magnetic blow out[permanent magnet or coil]

Such will usually require mounting vertically in the direction indicated to assist the arc blowing into the extinguisher area

]



__________________


Guru

Status: Offline
Posts: 5388
Date:

Thanks for that explanation, oldtrack123, it is appreciated



__________________

Tony

It cost nothing to be polite



Guru

Status: Offline
Posts: 1315
Date:

If you want a reliable DC circuit breaker for solar you can't go past the No Ark range. Those lever type DC circuit breakers have a nasty habit of getting hot and tripping well before they have reached their rated capacity due to poor contacts creating high resistance. There other specialty is welding the contacts together and never tripping.

T1 Terry

__________________

You can lead a head to knowledge but you can't make it think. One day I'll know it all, but till then, I'll keep learning.